Mechanical values and environment

Housing materialPolyamide PA6.6
Weight
Net 0,45 kg
Ambient temperature -20 ... 60 °C
Degree of protectionIP20
Mounting methodMounting rail 35mm according to DIN EN 6715 TH35
ConnectionConnection terminals
Safety contacts 1.14, 1.24, 2.14, 2.24
Number of safety contacts 2
Auxiliary contact terminals: L/+/1.Y1, L/+/2.Y1
Number of monitoring contacts 2
Terminals for the start buttons: 1.Y2, 2.Y2
Number of inputs 2

Electrical connection ratings

ASi voltage 18,5 ... 31,6 V
ASi operating currentmax.45 mA
Operating voltage DC
24 -15 ... +15 V DC  A power supply unit with electrical isolation in accordance with IEC 60742, PELV, must be used to power the safety monitor and all AS-Interface components.
Rated operating current Ie 200 mA
Rated thermal current Ith
Per output circuit 3 A
Fusing
External contact fuses (safety circuit) according to IEC 60269-14A medium slow-blow
Residual ripplemax.15 %
Overvoltage category according to IEC EN 60664-1 3
Connection cross-section
For wire1x(0.5...4.0)mm2, 2x(0.5...2.5)mm2
Flexible wire with cable end sleeve1x(0.5...2.5)mm2, 2x(0.5...1.5)mm2
2x AWG 20 to 14
Current via feedback loop
at 24 V DCOptocoupler input active high input current 10 mA
Response delaymax.40 ms
Switch-on delaymax.10 s
Max. contact load
DC-131A 24V
AC-153A 230V
ASi slave type
EA code: 7
ID code: F
Safety contacts 1.14, 1.24, 2.14, 2.24
Type of output
2 NO contacts per safety outputRelay contacts, floating, positively driven Positively driven relays according to EN50205
Auxiliary contact terminals: L/+/1.Y1, L/+/2.Y1
Type of outputSemiconductor output, 200 mA, short-circuit and reverse polarity protection
Terminals for the start buttons: 1.Y2, 2.Y2
Type of input
at 24 V DCOptocoupler input active high for start buttons, input current approx. 10 mA

Interface, bus

Data interfaceConnection socket for configuration

Miscellaneous

in compliance withEN ISO 13849Или отправьте нам запрос наC EN 60204-1, EN 50295
Function scopeBase

Reliability values acc. to EN ISO 13849-1

Performance LevelPL e
Category 4
PFHD9.1 x 10-9
SIL CL 3<