Safety Monitor, 16 decentralized output circuits

General specifications

AS-Interface specificationV3.0
PLC-Functionalitynone
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
Switch-on delay< 10 s
Response delay< 40 ms
UL File NumberE223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source

Functional safety related parameters

Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
MTTFd200 a
B10d2 E+7

Indicators/operating means

DisplayIlluminated graphical LC display for addressing and error messages
LED FAULTError display; red LED
red: Communication error
red flashing: release circuit error
LED POWERvoltage ON; LED green
LED U AS-i 1 / U AS-i 2AS-Interface voltage - circuit 1/circuit 2; green LED
LED readyoff: -
constantly lit: startup/restart lock active
flashing: external test required
LED AUXext. auxiliary voltage UAUX ; LED green
LED EDM/StartExternal device monitoring circuit inputs closed, 4x yellow LEDs
LED output circuitOutput circuit closed; 4 x green LEDs
Button4

Electrical specifications

Insulation voltage? 500 V
Rated operating voltage26.5 ... 31.6 V from AS-Interface;
24VDC
Rated operating current? 200 mA from 24VDC
? 45mA from AS-Interface

Interface

Interface typeRS 232, serial
Transfer rate19.6 kbaud, no parity, 1 start bit, 1 stop bit, 8 data bits

Interface 2

Interface typeChip card slot

Input

Number/Type4 EDM/Start inputs:
EDM: Inputs for the external device monitoring circuits
Start: start inputs:
Static switching current 4mA at 24V, dynamic 30mA at 24V (T=100?s)

Output

Safety outputOutput circuits 1 and 2: 2 potential-free contacts,
max. contact load:
3 ADC-13 at 30VDC,
3AAC-15 at 30VAC
Output circuits 3 and 4: 2 PNP transistor outputs
max. contact load:
0.5 ADC-13 at 30 VDC

Connection

AS-Interfacespring terminals, removable

Directive conformity

Electromagnetic compatibility

Standard conformity

Electromagnetic compatibilityEN61000-6-2:2005, EN61000-6-4:2007
Degree of protectionEN60529:2000
AS-InterfaceEN62026-2:2013
StandardsEN61000-6-2:2005, EN61000-6-4:2007 EN954-1:1996 (up to Kategorie 4), IEC61508:2001 and EN62061:2005 (up to SIL3) EN13849:2008 (PLe)